Add to Cart
Hall current sensors are mainly used to isolate and convert AC, DC, pulse and other complex signals .After signals are convertedaccording to the Hall Effect Theory,the can be directly acquired by AD, DSP, PLC, secondary instruments and other devices.Hall current sensors are widel applicable for acquisition and feedback control of current signals in the current monitoring,battery application,inverter,solar power management,direct current cabinet ,DC motor drive,electroplating,welding,frequency converter,UPS servo control systems.They feature the quick response ,wide range of measurement,high precision ,strong overload capcity,good linearity and excellent and anti-interference performace.
Electrical characteristics | ||||||||
Type | CS300EK2 | CS400EK2 | CS600EK2 | CS800EK2 | CS1000EK2 | CS2000EK2 | ||
IPN | Primary nominal input current | 300 | 400 | 600 | 800 | 1000 | 2000 | A |
IP | Measuring range of primary current | 0~±600 | 0~±800 | 0~±1200 | 0~±1600 | 0~±2000 | 0~±3000 | A |
VOUT | Nominal output voltage | 4±1% | V | |||||
VC | Supply voltage | ±12~±15(±5%) | V | |||||
IC | Current consumption | VC=±15V <25 | mA | |||||
VD | Insulation voltage | AC/50Hz/1min 5 | kV | |||||
εL | Linearity | <1 | %FS | |||||
VO | Offset voltage | TA=25℃ <±25 | mV | |||||
VOM | Residual voltage | IPN→0 <±25 | mV | |||||
VOT | Thermal drift of V0 | IP=0 TA=–25~+85℃ <±1 | mV/℃ | |||||
TR | Response time | ≤7 | μs | |||||
f | Frequency bandwidth(-3dB) | DC~20 | kHz | |||||
TA | Ambient operating temperature | –25~+85 | ℃ | |||||
TS | Ambient storage temperature | –40~+100 | ℃ | |||||
RL | Load resistance | ≥10 | KΩ | |||||
Standard | Q/3201CHGL02-2016 |